Subject: Velocity of water through a 1.5 inch ID pipe.
From: ACRE
Date: 11/21/2004, 4:10 PM


     Just for the heck of it I thought I would calculate
     the velocity of the water going through a 1.5 inch pipe.

     The area of the pipe is 1.77 square inches.
     A gallon is 235 cubic inches so the length of pipe
     needed to hold a gallon is 132 inches long or 11 feet.

     At 50 GPM that means water is moving down the pipe at
     550 feet per minute or 9 feet per second. 5 MPH.
     Not much.  Half the area would be 10 MPH. One quarter
     the area or 3/4 inch ID would be 20 MPH. Now we are getting
     up there. Inside the valve when the valve was nearly closed
     the water would be zinging along however the length of the valve
     is minimal so not much friction HP would be lost.

     To quote Kays and London again:

     "The design of a heat exchanger involves a consideration of both the heat
     transfer rates between the fluids and the mechanical pumping power expended
     to overcome fluid friction and move the fluids through the heat exchanger.
     For a heat exchanger operating with high-density fluids, the friction-power
     expenditure is generally small relative to the heat transfer rate, with the
     result that the friction-power expenditure is seldom of controlling
     influence."

     That may be true but it could be partially the cause of the high HP requirements
     we are seeing.

     "The friction-power expenditure is also increased with flow velocity, but in this
     case the power varies by as much as the cube of the velocity and never less
     than the square."

     Ah ha!!! So this is why we where blowing circuit breakers on one and two HP motors
     and why it took a five HP motor to pump water through the system at 7000 RPM and
     75 gallons a minute. Long passages in the radiator and engine block could
     generate considerable HP loses due to friction alone.

     Paul Lamar


Paul, as I recall the CW and Deere engine designs used 12 FPS as a maximum coolant velocity for hot zone coolant passages. This was because the occurence of cavitation erosion would increase
dramatically at higher velocities. (Cavitation erosion is very localized at the metal surface, and is influenced by metal temperature, vibration, coolant contaminants, and metal surface finish among
other factors. It is evidenced by tiny "worm holes" into the metal or in more severe cases spongelike erosion of the metal over a wider area.)

Jon Lauter
Rotary Power Marine Corporation

Good to get some actual engineering data from engine designers. Thanks Jon.

BTW Chuck Dunlap mentioned some deposits in his radiator after a few years.
Have you heard of this happening with anti freeze solutions when used
at 230 to 250 F?

Paul Lamar
 